MR-US1K / US1KA (tower UPS)
Protect your data and devices Power: 1 kVA / 1 kW
-
Умный Мини ИБП Постоянного тока
Серия KP3 | Непрерывное питание Wi-Fi
-
• High-frequency online double conversion with DSP control
• Efficiency up to 95.5% for energy savings
• Backup power supply in the event of overload or fault
• Increased application availability
• Real-time power status notification
• Temporary battery power during outages
• Intuitive control panel for quick status insight
• Control via serial interface ports
• Support for low-power operation
• High power factor of 1.0 PF
• Easy recovery from overloads
• Automatic self-diagnosis
• Intelligent battery management
• Wide input voltage range
隐藏域元素占位
- Обзор
- Характеристики
- Загрузки
- Поддержка
- Описание
-
Single-phase interactive IBT
1 kVA / 2 kVA / 3 kVA
Развернуть все
| Model | MR-US1K | MR-US2K | MR-US3K | MR-US6K | MR-US10K | ||||||||
| Rated power | 1kVA / 1kW | 2kVA / 2kW | 3kVA / 3kW | 6kVA / 6kW | 10kVA / 10kW | ||||||||
| Output | |||||||||||||
| Output voltage | 208 / 220 / 230 / 240VAC | ||||||||||||
| Output frequency | 50 / 60Hz ± 0.1% | ||||||||||||
| Output harmonic distortion | ≤3% THD (linear load), ≤5% THD (non-linear load) | ||||||||||||
| Output Power Factor | 1.0 | ||||||||||||
| Transfer Time | AC Mode 0ms to Battery Mode, Inverter 4ms Transfer (Typical) | ||||||||||||
| IBK Type | Online Double Conversion | ||||||||||||
| Waveform Type | Pure Sine Wave | ||||||||||||
| Input | |||||||||||||
| Rated Input Voltage | 208 / 220 / 230 / 240VAC | ||||||||||||
| Input Voltage Range | 110 – 300VAC, 110 – 176VAC, 280 – 300VAC (limited power) | ||||||||||||
| Input Frequency | 50 / 60 ± 6Hz (standard), ±10Hz (adjustable) | ||||||||||||
| Input Power Factor | >=0.99 | ||||||||||||
| Load Efficiency | |||||||||||||
| AC Mode | Full Load 94.5%@220VAC | Full Load 95.5%@220VAC | Full Load 95.5%@220VAC | Full Load Efficiency 95%, Maximum Efficiency 95.5% | |||||||||
| Battery mode | Full load 89.5%@36VDC | Full load 91.5%@72VDC | Full load 91.5%@96VDC | Full load efficiency 94.8% (20 batteries), Maximum efficiency 95.3% | |||||||||
| Battery | |||||||||||||
| Battery type | Lead acid battery | ||||||||||||
| Number of batteries | 12V / 7A·h * 2 | 12V / 7A*4 | 12V / 7A*6 | 12V / 7A/h (optional 9A/h) *16 | |||||||||
| Typical charging time | 4-5 hours to restore capacity to 90% | 7 – 9 hours to restore capacity to 90% | |||||||||||
| Physical characteristics | |||||||||||||
| Shape | Tower | ||||||||||||
| Dimensions, L*W*H (mm) | 276 * 145 * 225 | 392 * 145 * 225 | 395 * 190 * 325 | 460 * 190 * 615 | |||||||||
| Net weight (kg) | 8.6 | 14.3 | 20.5 | 50.6 | 50.8 | ||||||||
| Communication interface | RS232, USB, EPO | RS232, USB, EPO, SNMP, dry contact, service connector | |||||||||||
| Communication and control | |||||||||||||
| Control panel | Multi-function status and control LCD display | ||||||||||||
| Alarm | Alarm every 8 seconds when battery power is low | ||||||||||||
| Alarm every second when battery power is low sounds | |||||||||||||
| Overload warning every second | |||||||||||||
| Protection | Short circuit, overload, overcharge and overdischarge protection | ||||||||||||
| Environment | |||||||||||||
| Operating temperature | 0°C – 40°C | ||||||||||||
| Storage temperature | -15°C – 60°C (Battery: 0°C – 40°C) | ||||||||||||
| Relative Humidity | 20 – 95% (non-condensing) | ||||||||||||
| Noise Level | Less than 50 dB (1 meter from the surface) | ||||||||||||
| Standards and Approvals | |||||||||||||
| Safety | IEC / EN62040-1, IEC / EN60950-1 | ||||||||||||
| SMS | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 | ||||||||||||
Specifications are subject to change without notice and all product drawings are for reference only. Please contact MARSRIVA for the latest information and specifications.
| Model | MR-US1KA | MR-US2KA | MR-US3KA | MR-US6KA | MR-US10KA | ||||||||
| Rated power | 1kVA / 1kW | 2kVA / 2kW | 3kVA / 3kW | 6kVA / 6kW | 10kVA / 10kW | ||||||||
| Output | |||||||||||||
| Output voltage | 100 / 110 / 115 / 120 / 127VAC | ||||||||||||
| Output frequency | 50 / 60Hz ± 0.1% | ||||||||||||
| Output harmonic distortion | ≤2% THD (linear load), ≤4% THD (non-linear load) | ||||||||||||
| Output power factor | 1.0 | ||||||||||||
| Transfer time | AC mode 0ms to battery mode, Inverter 4ms transfer (typical) | ||||||||||||
| IBK type | Online double conversion | ||||||||||||
| Waveform type | Pure sine wave | ||||||||||||
| Input | |||||||||||||
| Rated Input Voltage | 100 / 110 / 115 / 120 / 127VAC | ||||||||||||
| Input Voltage Range | 110 – 300VAC, 110 – 176VAC, 280 – 300VAC (limited power) | ||||||||||||
| Input Frequency | 50 / 60 ± 6Hz (standard), ±10Hz (adjustable) | ||||||||||||
| Input Power Factor | >=0.99 | ||||||||||||
| Load Efficiency | |||||||||||||
| AC Mode | Full Load 93.5%@110VAC | Full Load 94.5%@110VAC | Full Load 94.5%@110VAC | Full Load Efficiency 95%, Maximum Efficiency 95.5% | |||||||||
| Battery Mode | Full Load 90.5%@36VDC | Full Load 93.5%@72VDC | Full Load 93.5%@96VDC | Full Load Efficiency 94.8% (20 batteries), Maximum Efficiency 95.3% | |||||||||
| Battery | |||||||||||||
| Battery type | Lead acid battery | ||||||||||||
| Number of batteries | 12V / 7A·h * 2 | 12V / 7A*4 | 12V / 7A*6 | 12V / 7A/h (optional 9A/h) *16 | |||||||||
| Typical charging time | 4-5 hours to restore capacity to 90% | 7 – 9 hours to restore capacity to 90% | |||||||||||
| Physical characteristics | |||||||||||||
| Shape | Tower | ||||||||||||
| Dimensions, L*W*H (mm) | 392*145*225 | 395*190*325 | 460 * 190 * 615 | ||||||||||
| Net weight (kg) | 9 | 15.6 | 20.7 | 91.8 | 104.8 | ||||||||
| Communication interface | RS232, USB, EPO | RS232, USB, EPO, SNMP, dry contact, maintenance connector | |||||||||||
| Communication and control | |||||||||||||
| Control panel | Multi-function status and control LCD display | ||||||||||||
| Alarm | Alarm sounds every 8 seconds when battery power is low | ||||||||||||
| Alarm sounds every second when battery power is low | |||||||||||||
| Alarm sounds every second when battery power is low | |||||||||||||
| Alarm sounds every second when overload warning | |||||||||||||
| Protection | Short circuit, overload, overcharge and overdischarge protection | ||||||||||||
| Environment | |||||||||||||
| Operating temperature | 0°C – 40°C | ||||||||||||
| Storage temperature | -15°C – 60°C (Battery: 0°C – 40°C) | ||||||||||||
| Relative Humidity | 20 – 95% (non-condensing) | ||||||||||||
| Noise Level | Less than 50dB (1 meter from the surface) | ||||||||||||
| Standards and Approvals | |||||||||||||
| Safety | IEC / EN62040-1, IEC / EN60950-1 | ||||||||||||
| SMS | IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8 | ||||||||||||
Specifications are subject to change without notice and all product drawings are for reference only. Please contact MARSRIVA for the latest information and specifications.
Загрузки
Извините, текущая колонка обновляется
Пожалуйста, оставайтесь настроенной!
Поддержка
Пожалуйста, обратитесь в наш отдел технической поддержки по вопросам установки, устранения неполадок или по общим вопросам, связанным с продуктом.
Часы работы: Пн – Пт, с 9:00 до 19:00 UTC+8
Обратитесь в службу технической поддержки: Отправить заявку сейчас
Отправить запрос в службу поддержки
Отправить билет поддержки